Register    Login    Forum    Search    FAQ

Board index » Programming Alarm Modems » PLC connectivity




Post new topic Reply to topic  [ 21 posts ]  Go to page 1, 2  Next
Author Message
 Post Posted: Fri Apr 18, 2008 10:20 pm 
Offline
Newbee

Joined: Fri Apr 18, 2008 9:55 pm
Posts: 10
Hi am trying to datalog the plc (ABB CL-LMR) input and outputs but I get no data.How do I get to know if the TAM is communicating with the PLC through TILA and log plc variables and send logged data via email?
will appreciate any hepl.


Top 
 Profile  
Reply with quote  
 Post subject:
 Post Posted: Sat Apr 19, 2008 9:31 am 
Offline
Tixi-Support-Team

Joined: Mon Oct 10, 2005 1:40 pm
Posts: 94
Location: Berlin
If TAM is correctly communicating with the PLC, the automatic generated system variable "Device State" will be set to "1".
Which TILA-Version, modem type and FW version are you using ?

_________________
Tixi Support Team

E-Mail-Support, Mo-Fr, 9:00am - 5:00pm, Tixi-Support@tixi.com
Support-Hotline, Mo-Fr, 9:00am - 5:00pm, +49-30-406 08 300


Top 
 Profile  
Reply with quote  
 Post Posted: Sat Apr 19, 2008 11:16 am 
Offline
Newbee

Joined: Fri Apr 18, 2008 9:55 pm
Posts: 10
Tixi-Support wrote:
If TAM is correctly communicating with the PLC, the automatic generated system variable "Device State" will be set to "1".
Which TILA-Version, modem type and FW version are you using ?



How do i check device state
Am using TILA Ver. 2.2.0.220,modem HG 27 . FW didnt understand!


Top 
 Profile  
Reply with quote  
 Post Posted: Mon Apr 21, 2008 8:30 am 
Offline
Tixi-Support-Team

Joined: Mon Oct 10, 2005 1:40 pm
Posts: 94
Location: Berlin
MainaE wrote:
How do i check device state !

If TILA is connected to the modem, the variable list offers a function "read variables" to refresh the table. There is a variable with type "PLC Device State" which will have the value 0 (failure) or 1 (OK).

MainaE wrote:
Am using TILA Ver. 2.2.0.220,modem HG 27 . FW didnt understand!

FW = Firmware Version (Alarm Modem -> Properties).
Which PLC type did you choose in TILA ? For the new CL series you'll have to choose Moeller Easy 500/700 (ABB CL is an OEM version it).

_________________
Tixi Support Team

E-Mail-Support, Mo-Fr, 9:00am - 5:00pm, Tixi-Support@tixi.com
Support-Hotline, Mo-Fr, 9:00am - 5:00pm, +49-30-406 08 300


Top 
 Profile  
Reply with quote  
 Post Posted: Mon Apr 21, 2008 2:36 pm 
Offline
Newbee

Joined: Fri Apr 18, 2008 9:55 pm
Posts: 10
Tixi-Support wrote:
MainaE wrote:
How do i check device state !

If TILA is connected to the modem, the variable list offers a function "read variables" to refresh the table. There is a variable with type "PLC Device State" which will have the value 0 (failure) or 1 (OK).

MainaE wrote:
Am using TILA Ver. 2.2.0.220,modem HG 27 . FW didnt understand!

FW = Firmware Version (Alarm Modem -> Properties).
Which PLC type did you choose in TILA ? For the new CL series you'll have to choose Moeller Easy 500/700 (ABB CL is an OEM version it).


Thats fine. My FW 2.2.0 and followed.
Am currently experiencing a new problem. Am able to upload soft from TAM but when i try to load from PC to TAM (same project or different) i get the following error:

Upload Failed!
The Alarm modem did not respond in time.
Please increase the communication timeout at Options-> Connection.

Have tried all the 4 timeout options and none seems to work.
I cant proceed further due to this error.


Top 
 Profile  
Reply with quote  
 Post Posted: Mon Apr 21, 2008 2:57 pm 
Offline
Tixi-Support-Team

Joined: Mon Oct 10, 2005 1:40 pm
Posts: 94
Location: Berlin
MainaE wrote:
Thats fine. My FW 2.2.0 and followed.

No, that's only the display for the compatibility mode ! I meant the firmware version number in the modem properties. It should be 2.0.0.0 or 2.2.12.0. Only the 2.2.12.0 supports ABB CL !

MainaE wrote:
Am currently experiencing a new problem. Am able to upload soft from TAM but when i try to load from PC to TAM (same project or different) i get the following error:

Did you try to factory reset the modem ? Can you email us the TILA project and TILA-Log to reproduce the problem ?

_________________
Tixi Support Team

E-Mail-Support, Mo-Fr, 9:00am - 5:00pm, Tixi-Support@tixi.com
Support-Hotline, Mo-Fr, 9:00am - 5:00pm, +49-30-406 08 300


Top 
 Profile  
Reply with quote  
 Post subject:
 Post Posted: Mon Apr 21, 2008 4:19 pm 
Offline
Tixi-Support-Team

Joined: Mon Oct 10, 2005 1:40 pm
Posts: 94
Location: Berlin
Thank you for the logfile. It seems that the COM2 of your HG27 is faulty.
Please try to factory reset your Alarm Modem. If it doesn't fix the problem, contact your dealer for warranty.

_________________
Tixi Support Team

E-Mail-Support, Mo-Fr, 9:00am - 5:00pm, Tixi-Support@tixi.com
Support-Hotline, Mo-Fr, 9:00am - 5:00pm, +49-30-406 08 300


Top 
 Profile  
Reply with quote  
 Post subject: COM Port
 Post Posted: Mon Apr 21, 2008 7:48 pm 
Offline
Newbee

Joined: Fri Apr 18, 2008 9:55 pm
Posts: 10
Tixi-Support wrote:
Thank you for the logfile. It seems that the COM2 of your HG27 is faulty.
Please try to factory reset your Alarm Modem. If it doesn't fix the problem, contact your dealer for warranty.


The ABB CL- LMR plc is connected via Com 2 and PC serial cable via Com 1. Any difference?


Top 
 Profile  
Reply with quote  
 Post subject: Re: COM Port
 Post Posted: Mon Apr 21, 2008 7:53 pm 
Offline
Newbee

Joined: Fri Apr 18, 2008 9:55 pm
Posts: 10
MainaE wrote:
Tixi-Support wrote:
Thank you for the logfile. It seems that the COM2 of your HG27 is faulty.
Please try to factory reset your Alarm Modem. If it doesn't fix the problem, contact your dealer for warranty.


The ABB CL- LMR plc is connected via Com 2 and PC serial cable via Com 1. Any difference?

The unit was bought from you last year 2007.


Top 
 Profile  
Reply with quote  
 Post subject: Re: COM Port
 Post Posted: Tue Apr 22, 2008 7:51 am 
Offline
Tixi-Support-Team

Joined: Mon Oct 10, 2005 1:40 pm
Posts: 94
Location: Berlin
MainaE wrote:
The ABB CL- LMR plc is connected via Com 2 and PC serial cable via Com 1. Any difference?

That's how it should work. In your TILA.log i can see that the Alarm Modem doesn't detect its COM2. -> hardware failure

MainaE wrote:
The unit was bought from you last year 2007.

Please contact our support team via email for RMA process.

_________________
Tixi Support Team

E-Mail-Support, Mo-Fr, 9:00am - 5:00pm, Tixi-Support@tixi.com
Support-Hotline, Mo-Fr, 9:00am - 5:00pm, +49-30-406 08 300


Top 
 Profile  
Reply with quote  
 Post subject: Re: COM Port
 Post Posted: Tue Apr 22, 2008 1:27 pm 
Offline
Newbee

Joined: Fri Apr 18, 2008 9:55 pm
Posts: 10
Tixi-Support wrote:
MainaE wrote:
The ABB CL- LMR plc is connected via Com 2 and PC serial cable via Com 1. Any difference?

That's how it should work. In your TILA.log i can see that the Alarm Modem doesn't detect its COM2. -> hardware failure

MainaE wrote:
The unit was bought from you last year 2007.

Please contact our support team via email for RMA process.


Have attached new prog for HG23-M.Still No plc communication.


Top 
 Profile  
Reply with quote  
 Post subject: Re: COM Port
 Post Posted: Tue Apr 22, 2008 1:42 pm 
Offline
Tixi-Support-Team

Joined: Mon Oct 10, 2005 1:40 pm
Posts: 94
Location: Berlin
MainaE wrote:
Have attached new prog for HG23-M.Still No plc communication.

I've received it. The configuration of the PLC communication seems to be OK. Is the ABB CL secured by an interface password ?
Are you able to access the ABB CL trough the modem using the ABB software (TILA connection type "PLC local at Alarm Modem, using 4800bps, 8N1, DeactivateDTR) ?

_________________
Tixi Support Team

E-Mail-Support, Mo-Fr, 9:00am - 5:00pm, Tixi-Support@tixi.com
Support-Hotline, Mo-Fr, 9:00am - 5:00pm, +49-30-406 08 300


Top 
 Profile  
Reply with quote  
 Post subject:
 Post Posted: Tue Apr 22, 2008 1:45 pm 
Offline
Tixi-Support-Team

Joined: Mon Oct 10, 2005 1:40 pm
Posts: 94
Location: Berlin
I've located the problem: you've forgotten to add PLC variables within TILA ! The modem needs to know which variable to query, so you have to add all variables, that you want to use for data logging or alarming...

_________________
Tixi Support Team

E-Mail-Support, Mo-Fr, 9:00am - 5:00pm, Tixi-Support@tixi.com
Support-Hotline, Mo-Fr, 9:00am - 5:00pm, +49-30-406 08 300


Top 
 Profile  
Reply with quote  
 Post subject:
 Post Posted: Tue Apr 22, 2008 2:09 pm 
Offline
Newbee

Joined: Fri Apr 18, 2008 9:55 pm
Posts: 10
Tixi-Support wrote:
I've located the problem: you've forgotten to add PLC variables within TILA ! The modem needs to know which variable to query, so you have to add all variables, that you want to use for data logging or alarming...


Let me try it and
I do have a serial port password but TILA has no option for this. I think we a have to do it via TICO if I have to preserve the password.
any guidance to do thru TICO?


Top 
 Profile  
Reply with quote  
 Post subject:
 Post Posted: Tue Apr 22, 2008 2:16 pm 
Offline
Tixi-Support-Team

Joined: Mon Oct 10, 2005 1:40 pm
Posts: 94
Location: Berlin
MainaE wrote:
I do have a serial port password but TILA has no option for this.

That's not supported. You'll have to remove the serial password, but you can keep the program password.

_________________
Tixi Support Team

E-Mail-Support, Mo-Fr, 9:00am - 5:00pm, Tixi-Support@tixi.com
Support-Hotline, Mo-Fr, 9:00am - 5:00pm, +49-30-406 08 300


Top 
 Profile  
Reply with quote  
Display posts from previous:  Sort by  
 
Post new topic Reply to topic  [ 21 posts ]  Go to page 1, 2  Next

Board index » Programming Alarm Modems » PLC connectivity


Who is online

Users browsing this forum: No registered users and 5 guests

 
 

 
You cannot post new topics in this forum
You cannot reply to topics in this forum
You cannot edit your posts in this forum
You cannot delete your posts in this forum
You cannot post attachments in this forum

Search for:
Jump to:  
cron