Hi Janez,
we have also a forum in english language.
Please use it for further posts.
See link
"English Forum" at the top..
Thanks !
veselja hat geschrieben:
Hi
Is possible to connect computer with 56k normal modem to PLC(mitsubishi melsec fx2n) with GSM alarm modem m20, without "R-CON RS 232 remote bridge tool"?? I tried to connect with GX Developer but it didn't work.
Janez
At first we recommend to use "MX-MAE Alarm Editor". The "connection" dialog offers the same functionality as "R-CON".
A connection with a "normal" 56k Modem to a MAM-GM20 is possible, but you have to use "GX IEC Developer" instead of "GX Developer".
See the Startup-Document
TAM-TransMode_with_Mitsubishi-FX.pdf on our webseite for further information and GX IEC settings.