Autor |
Nachricht |
Sersch80
|
Verfasst: Mi Sep 26, 2007 1:24 pm |
|
Registriert: Mo Jun 11, 2007 9:07 am Beiträge: 82
|
|
|
|
|
Tixi-Support
|
Verfasst: Mi Sep 26, 2007 1:14 pm |
|
Registriert: Mo Jul 11, 2005 5:50 pm Beiträge: 1351 Wohnort: Berlin
|
Sersch80 hat geschrieben: Code: [<SetConfig _="LOG" ver="y"> <LogDefinition> <LogFiles> <JobReport size="10240"/> <Event size="10240"/> <Login size="10240"/> <IncomingMessage size="10240"/> <FailedIncomingCall size="10240"/> <SupportLog size="10240"/> <Datalogging_0 size="31000" contenttype="binary" record="Datalogging_0"/> </LogFiles> <Records> <Datalogging_0> <Variable_1 _="Unit32" path="/Process/Bus1/Device_0/Variable_1"/> <Variable_0 _="Uint32" path="/Process/Bus1/Device_0/Variable_0"/>
</Datalogging_0> </Records> </LogDefinition> </SetConfig>]
Code: [<SetConfig _="LOG" ver="y"> <LogDefinition> <LogFiles> <JobReport size="10240"/> <Event size="10240"/> <Login size="10240"/> <IncomingMessage size="10240"/> <FailedIncomingCall size="10240"/> <SupportLog size="10240"/> <Datalogging_0 size="31000" contenttype="binary" record="Datalogging_0"/> </LogFiles> <Records> <Datalogging_0> <Variable_1 _="float" path="/Process/Bus1/Device_0/Variable_1"/> <Variable_0 _="float" path="/Process/Bus1/Device_0/Variable_0"/>
</Datalogging_0> </Records> </LogDefinition> </SetConfig>]
Sollte die von der SPS gelesenen Uint32-Werte als Float-Werte loggen.
_________________ Tixi Support Team
E-Mail-Support, Mo-Fr, 9:00 - 17:00: Tixi-Support@tixi.com
techn. Hotline, Mo-Fr, 9:00 - 12:00 und 13:00 - 17:00: 0900-100 90 11 für 2€/min
|
|
|
|
|
Sersch80
|
Verfasst: Mi Sep 26, 2007 1:01 pm |
|
Registriert: Mo Jun 11, 2007 9:07 am Beiträge: 82
|
Code: [<SetConfig _="PROCCFG" ver="y"> <External> <Bus Name="Bus1" _="COM2" family="Siemens" Product="S7-300/400-A" protocol="Siemens,S7-300/400-A" baud="115200" handshake="none" type="Master" TS="1" MAXADR="15" GUF="1" RC="1"> <Device Name="Device_0" NameUser="S7-300/400-A" _="2" Pollrate="1s"> <Variable_0 Name="Gesamtbezug Arbeit" _="DBD" simpleType="Uint32" db="3" ind="104" acc="R"/> <Variable_1 Name="Gasgesamzbezug Leistung" _="DBD" simpleType="Uint32" db="3" ind="108" acc="R"/> </Device> </Bus> </External> </SetConfig>]
|
|
|
|
|
Sersch80
|
Verfasst: Mi Sep 26, 2007 12:36 pm |
|
Registriert: Mo Jun 11, 2007 9:07 am Beiträge: 82
|
Code: [<SetConfig _="LOG" ver="y"> <LogDefinition> <LogFiles> <JobReport size="10240"/> <Event size="10240"/> <Login size="10240"/> <IncomingMessage size="10240"/> <FailedIncomingCall size="10240"/> <SupportLog size="10240"/> <Datalogging_0 size="31000" contenttype="binary" record="Datalogging_0"/> </LogFiles> <Records> <Datalogging_0> <Variable_1 _="Unit32" path="/Process/Bus1/Device_0/Variable_1"/> <Variable_0 _="Uint32" path="/Process/Bus1/Device_0/Variable_0"/>
</Datalogging_0> </Records> </LogDefinition> </SetConfig>]
[/quote]
|
|
|
|
|
Tixi-Support
|
Verfasst: Mi Sep 26, 2007 12:34 pm |
|
Registriert: Mo Jul 11, 2005 5:50 pm Beiträge: 1351 Wohnort: Berlin
|
Sersch80 hat geschrieben: Hi, ich versuche mit einem HM71 zwei Realwerte aus einer S7-300zu loggen. Das Tixi loggt die Werte, aber als Dezimalwerte ohne kommastellen (d.h. geloggt wird die Zahl 107500115 statt 2,3). wie bekomme ich es eingestellt dass werte richtig geloggt werden.
Wie sieht die Definition der SPS-Variablen und die Loganweisung aus?
_________________ Tixi Support Team
E-Mail-Support, Mo-Fr, 9:00 - 17:00: Tixi-Support@tixi.com
techn. Hotline, Mo-Fr, 9:00 - 12:00 und 13:00 - 17:00: 0900-100 90 11 für 2€/min
|
|
|
|
|
Sersch80
|
Verfasst: Mi Sep 26, 2007 11:33 am |
|
Registriert: Mo Jun 11, 2007 9:07 am Beiträge: 82
|
Hi, ich versuche mit einem HM71 zwei Realwerte aus einer S7-300zu loggen.
Das Tixi loggt die Werte, aber als Dezimalwerte ohne kommastellen (d.h. geloggt wird die Zahl 107500115 statt 2,3). wie bekomme ich es eingestellt dass werte richtig geloggt werden.
|
|
|
|
|
|